Flash point
The flash point of a volatile material is the lowest temperature at which it can vaporize to form an ignitable mixture in air. Measuring a flash point requires an ignition source. At the flash point, the vapor may cease to burn when the source of ignition is removed.
The flash point is not to be confused with the autoignition temperature, which does not require an ignition source, or the fire point, the temperature at which the vapor continues to burn after being ignited. Neither the flash point nor the fire point is dependent on the temperature of the ignition source, which is much higher.
The flash point is often used as a descriptive characteristic of liquid fuel, and it is also used to help characterize the fire hazards of liquids. “Flash point” refers to both flammable liquids and combustible liquids. There are various standards for defining each term. Liquids with a flash point less than 60.5 °C (140.9 °F) or 37.8 °C (100.0 °F)—depending upon the standard being applied—are considered flammable, while liquids with a flash point above those temperatures are considered combustible.[1]
Mechanism
Every liquid has a vapor pressure, which is a function of that liquid's temperature. As the temperature increases, the vapor pressure increases. As the vapor pressure increases, the concentration of vapor of the flammable liquid in the air increases. Hence, temperature determines the concentration of vapor of the flammable liquid in the air.
A certain concentration of vapor in the air is necessary to sustain combustion, and that concentration is different for each flammable liquid. The flash point of a flammable liquid is the lowest temperature at which there will be enough flammable vapor to ignite when an ignition source is applied.
Measurement
There are two basic types of flash point measurement: open cup and closed cup.
In open cup devices the sample is contained in an open cup which is heated, and at intervals a flame is brought over the surface. The measured flash point will actually vary with the height of the flame above the liquid surface, and at sufficient height the measured flash point temperature will coincide with the fire point. The best known example is the Cleveland open cup (COC).
There are two types of closed cup testers: non-equilibrium, such as Pensky-Martens where the vapors above the liquid are not in temperature equilibrium with the liquid, and equilibrium, such as Small Scale (commonly known as Setaflash) where the vapors are deemed to be in temperature equilibrium with the liquid. In both these types the cups are sealed with a lid through which the ignition source can be introduced. Closed cup testers normally give lower values for the flash point than open cup (typically 5–10 °C lower, or 9–18 °F lower) and are a better approximation to the temperature at which the vapor pressure reaches the lower flammable limit.
The flash point is an empirical measurement rather than a fundamental physical parameter. The measured value will vary with equipment and test protocol variations, including temperature ramp rate (in automated testers), time allowed for the sample to equilibrate, sample volume and whether the sample is stirred.
Methods for determining the flash point of a liquid are specified in many standards. For example, testing by the Pensky-Martens closed cup method is detailed in ASTM D93, IP34, ISO 2719, DIN 51758, JIS K2265 and AFNOR M07-019. Determination of flash point by the Small Scale closed cup method is detailed in ASTM D3828 and D3278, EN ISO 3679 and 3680, and IP 523 and 524.
Examples
Fuel | Flash point | Autoignition temperature |
---|---|---|
Ethanol (70%) | 16.6 °C (61.9 °F)[2] | 363 °C (685 °F)[2] |
Gasoline (petrol) | −43 °C (−45 °F)[3] | 280 °C (536 °F)[4] |
Diesel | >62 °C (144 °F) | 210 °C (410 °F) |
Jet fuel | >60 °C (140 °F) | 210 °C (410 °F) |
Kerosene (paraffin oil) | >38–72 °C (100–162 °F) | 220 °C (428 °F) |
Vegetable oil (canola) | 327 °C (621 °F) | |
Biodiesel | >130 °C (266 °F) |
Gasoline (petrol) is a fuel for use in a spark-ignition engine. The fuel is mixed with air within its flammable limits and heated above its flash point, then ignited by the spark plug. In order to avoid preignition by dint of the hot combustion chamber, the fuel must have a low flash point and a high autoignition temperature.
Diesel fuel flash points vary between 52 and 96 °C (126 and 205 °F). Diesel is suitable for use in a compression-ignition engine. Air is compressed until it has been heated above the autoignition temperature of the fuel, which is then injected as a high-pressure spray, keeping the fuel-air mix within flammable limits. In a diesel-fueled engine, there is no ignition source (such as the spark plugs in a gasoline engine). Consequently, diesel fuel must have a high flash point and a low autoignition temperature.
Jet fuel flash points also vary. Both Jet A and Jet A-1 have flash points between 38 and 66 °C (100 and 151 °F), close to that of off-the-shelf kerosene. Yet both Jet B and JP-4 have flash points between −23 and −1 °C (−9 and 30 °F).
Standardization
Flash points of substances are measured according to standard test methods. These test methods define the apparatus required to carry out the measurement, key test parameters, the procedure for the operator or automated apparatus to follow, and the precision of the test method.
Standard test methods are written and controlled by a number of national and international committees and organizations. The three main bodies are the CEN / ISO Joint Working Group on Flash Point (JWG-FP), ASTM D02.8B Flammability Section and the Energy Institute's TMS SC-B-4 Flammability Panel.
References
- ↑ NFPA 30: Flammable and Combustible Liquids Code, 2012 Edition Retrieved January 23, 2012.
- ↑ 2.0 2.1 Ethanol MSDS Retrieved January 23, 2012.
- ↑ "Flash Points — Fuels". http://www.engineeringtoolbox.com/flash-point-fuels-d_937.html. Retrieved January 23, 2012.
- ↑ "Fuels and Chemicals — Auto Ignition Temperatures". http://www.engineeringtoolbox.com/fuels-ignition-temperatures-d_171.html. Retrieved January 23, 2012.
ar:نقطة الوميض bg:Температура на запалване bs:Tačka paljenja ca:Punt d'inflamabilitat cs:Teplota vzplanutí da:Flammepunkt de:Flammpunkt et:Leektemperatuur es:Punto de inflamabilidad fa:نقطه اشتعال fr:Point d'éclair ko:인화점 it:Punto di infiammabilità he:נקודת הבזק lt:Pliūpsnio temperatūra hu:Lobbanáspont mk:Температура на запалување nl:Vlampunt ja:引火点 no:Flammepunkt nn:Flammepunkt pl:Temperatura zapłonu pt:Ponto de fulgor ro:Temperatură de aprindere ru:Температура вспышки simple:Flash point sk:Teplota vzplanutia sl:Plamenišče sr:Tačka paljenja fi:Leimahduspiste sv:Flampunkt uk:Температура займання ur:نقطۂ شرار zh:闪点